| Products : Industrial Sector : UPS : UPS:Supernova Series : Rating 160 to 300 kVA.( 8 Unit parallelable upto 2400 kVA) |
 |
| |
 |
Supernova Series : Rating 160 to 300 kVA.( 8 Unit parallelable upto 2400 kVA) |
|
|
|
| |
|
|
|
| |
|
|
Product
Details |
 |
| |
|
|
Autometers Alliance Ltd ranks amongst the premier UPS manufacturers in the country and offers top-of-the-line Pegasus UPS systems.Supernova model conforms to IEC801-2, IEC801-3, IEC801-4, IEC146-4, IEC950, EN50091-1 and IE50091-2 Class A. |
| |
|
|
|
| |
|
|
Salient
Features |
 |
| |
|
|
- Microprocessor Based Double
- Conversion Topology
- Active Power Factor Correction at
- UPS Input
- High Frequency PWM Based Inverter
- Using IGBTs
- Auto Re-transfer Static Switch
- Energy SavingMode
- Control Panel with LCD Display,
- Emergency Power Off integrated
- Cold Start
- Parallel Redundancy upto 8 units
- Interface for Teleservice
- WATER COOLED SYSTEMS
Options
- 12 Pulse Rectifier at UPS Input
- Harmonic Filter at UPS Input
- Isolation Transformer at UPS Input and Output
- Management Software
- Remote Monitor for Alarms /
- Indications
- Remote Emergency Power Off
- Potential free contacts for Remote
- indications
- SNMPAdapter
- Voltage stabiliser in Bypass Line
- Battery Management System
- Teleservice
|
| |
|
|
|
| |
|
|
Technical
Specifications |
| |
|
|
|
kVA/kW |
160/128 |
200/160 |
250/200 |
300/240 |
| Input power factor |
>.97(standard), >.99(optional) |
| Input voltage 3ø+N |
380/400/415VAC 340-460VAC |
| Input frequency |
50 or 60Hz 40-70Hz |
| Output voltage 3ø+N |
380/400/415VAC±1% |
| Output frequency |
50 or 60Hz, ±1%, ±2%, ±5%,±10%(selectable) in synchronism with grid 50 or 60Hz ±0.005% with oscillator |
| Output wave form |
Sinewave |
| Output distortion |
<3% with linear load |
| Type of battery |
SMF/Ni-cd/Tubular |
| Dimensions WxDxH mm |
(*200+1040) x 800 x 1800 |
| Weight Kg. |
490 |
550 |
600 |
680 |
| Cooling |
Water cooled |
|
Conformance to International standards |
IEC801-2, IEC801-3, IEC801-4, IEC146-4, IEC950, EN50091-1 and EN50091-2 class A | |
| |
|
|
|
| |
|
|
|
|
| |
| |
| |
|
|