| Products : Industrial Sector : UPS : UPS:Atlas Series : Rating 60 to 120 kVA (8 Unit parallelable upto 960 kVA) |
 |
| |
 |
Atlas Series : Rating 60 to 120 kVA (8 Unit parallelable upto 960 kVA) |
|
|
|
| |
|
|
|
| |
|
|
Product
Details |
 |
| |
|
|
Autometers Alliance Ltd ranks amongst the premier UPS manufacturers in the country and offers top-of-the-line Pegasus UPS systems. Atlas model conforms to IEC801-2, IEC801-3,IEC801-4,IEC146-4, IEC950,EN50091-1 and EN50091-2 Class A. |
| |
|
|
|
| |
|
|
Salient
Features |
 |
| |
|
|
- Microprocessor Based Double Conversion Topology
- High Frequency PWM Based inverter using IGBTs
- Auto Re-transfer Static Switch
- Energy Saving Mode
- Control Panel with LCD Display
- Emergency Power Off integrated
- Cold Start
- Parallel Redundancy up to 8 units
- Interface for Teleservice
Options
- 12 Pulse Rectifier at UPS Input
- Harmonic Filter at UPS Input
- Isolation Transformer at UPS Input and Output
- Management Software
- Remote Monitor for Alarms/Indications
- Remote Emergency Power Off
- Potential free contacts for Remote Indications
- SNMP Adapter
- Voltage stabiliser in Bypass Line
- Battery Management System
- Teleservice
|
| |
|
|
|
| |
|
|
Technical
Specifications |
| |
|
|
|
kVA/kW |
60/48 |
80/64 |
100/80 |
120/96 |
| Input power factor |
>0.95 (standard), >.99(optional) |
| Input voltage 3ø+N |
380/400/415VAC 350-460VAC |
| Input frequency |
50 or 60Hz 40-70Hz |
| Output voltage 3ø+N |
380/400/415 Vac ±1% |
| Output frequency |
50 or 60Hz, ±1%, ±2%, ±5%,±10%(selectable) in synchronism with grid 50 or 60Hz ±0.005% with internal oscillator |
| Output wave form |
Sinewave |
| Output voltage distortion |
<3% with linear load |
| Type of battery |
SMF/Ni-cd/Tubular |
| Dimensions WxDxH mm |
700 x 740 x 1800 |
| Weight kg. |
300 |
335 |
365 |
455 |
| Cooling |
Forced Air |
|
Conformance to Internationa standards |